Skip to content
A2ZCalc

Thermal Resistance Converter

Convert thermal resistance, the temperature difference per unit of power.

Written by Rahman · Last reviewed

Quick answer

Thermal resistance measures opposition to heat flow, in kelvin per watt. One degree Celsius per watt is identical because the interval sizes match, and one °F·h/BTU is 1.8956 K/W. A CPU heatsink rated at 0.5 K/W will sit 50 °C above ambient when dissipating 100 watts.

1
1 K/W = 1 °C/W
1 Kelvin per watt in all units
Kelvin per watt (K/W)1
Degree Celsius per watt (°C/W)1
Degree Fahrenheit hour per BTU (°F·h/BTU)0.5275279263

About the Thermal Resistance Converter

Thermal resistance measures how strongly a material or assembly resists the flow of heat. A higher value means better insulation. The SI unit is the kelvin per watt.

It is widely used in building insulation and electronics cooling.

Absolute resistance and R-value are different quantities

This converter handles absolute thermal resistance (kelvin per watt), which describes a specific object: this heatsink, this wall assembly, this component package. It answers how much temperature difference a given heat flow produces across that particular thing.

Insulation R-value is a different quantity. It is area-specific, measured in square metres kelvin per watt or square feet degree Fahrenheit hours per BTU, and describes a material per unit of area rather than a finished object. The two are related by area, so an R-value cannot be converted here without knowing how large the surface is.

  • Absolute resistance falls as area rises: doubling the area of the same insulation halves the resistance of the assembly while leaving its R-value unchanged.
  • U-value is the reciprocal of area-specific resistance. Lower is better for U, higher is better for R, which is why the two are so often confused.
  • Electronics cooling works almost entirely in absolute terms, quoting junction-to-ambient resistance in K/W or °C/W. Those two units are numerically identical, since an interval of one kelvin equals an interval of one degree Celsius.

US R-values and metric RSI are not the same numbers

Insulation is labelled R-19 or R-30 in the US and RSI 3.0 or RSI 5.0 in metric markets, and the numbers are not comparable. The US unit combines square feet, degrees Fahrenheit, hours and BTU; the metric RSI uses square metres, kelvin and watts.

Working the conversion through this site's own factors (a square foot is 0.09290304 m² and a °F·h/BTU is 1.8956342406 K/W) gives a ratio of about 5.678. So RSI 1 is roughly R-5.68, R-19 is about RSI 3.35, and RSI 3.0 is about R-17.

  • A product labelled R-3 in a metric market is a very different material from one labelled R-3 in the US.
  • Assembly R-value is lower than the sum of its materials, because studs, joists and fixings conduct around the insulation: thermal bridging.
  • Rated values assume correct installation. Compressed or gapped insulation performs below its label.

Frequently Asked Questions

What is thermal resistance?

⌄

It is the temperature difference required to drive one unit of heat power through a material, the opposite of thermal conductance.

Does a higher value mean better insulation?

⌄

Yes. Higher thermal resistance means heat flows through more slowly, which is desirable for insulation.

Where is it used?

⌄

It is used in building design, where it relates to R-values, and in electronics for managing heat from components.

More Heat Converters